This page summarizes BK Resources' installation instructions for its gas connector hoses and connection kits. It is not a substitute for the BK manual that ships with each hose; download the full manual and spec sheet from any product page. BK requires that all installation and testing be done by qualified personnel.
Codes and standards
- Installation must comply with the National Fuel Gas Code (ANSI Z223.1) and local gas installation codes.
- BK gas hoses comply with ANSI Z21.69 • CSA 6.16 for connectors for movable gas appliances. BK's optional quick connect complies with ANSI Z21.41 • CSA 6.9.
- The quick connect is approved for 1st, 2nd and 3rd family gases under 50 mbar pressure. Maximum fuel gas pressure through it is 1/2 psi (3.5 kPa).
Before you start
- Shut off the main gas line and the connecting ball valve so there is no gas flow.
- Choose the hose length for the job. Gas lines and stub-outs vary, so pick a length that installs with no kinks, twists or excessive bends.
- Offset the two ends of the hose from each other to keep the appliance as close to the wall as possible.
- An approved manual shut-off ball valve is required at the connection from the gas line to the hose, within 6" of the appliance.
- The gas outlet may not be hidden in or covered by drywall, flooring or partition walls.
- Any quick connect must be sized to match the hose.
Configuration 1: with a quick connect
Appliance side: seal the appliance NPT stub-out and attach a 90° female-to-male elbow. Seal its male end and attach the male (nipple) half of the quick connect, checking the gas-flow direction. Seal one end of the hose and thread on the female half of the quick connect, again checking flow direction.
Gas supply side: seal the supply nipple and install the ball valve, using the kit's 90° elbow if it helps position the hose. Seal the hose threads, thread the hose into the valve, then join the two halves of the quick connect.
Configuration 2: valve only, no quick connect
Appliance side: seal the NPT stub-out, attach a 90° female-to-female elbow, then thread the sealed hose end into it.
Gas supply side: seal the supply nipple, add the 90° elbow if needed, install the ball valve and thread the hose into it.
Tighten every connection with wrenches.
Restraining cable
The restraining cable must be installed and connected whenever the hose is installed. It keeps the hose from being pulled beyond its limits. BK's 5-year hose warranty requires a BK Resources restraining cable kit.
- Fasten the cable bracket to the wall with the four screws provided, into studs, metal or wood where possible. Use the plastic anchors if there's no stud.
- Before drilling the appliance, make sure the bit won't hit any operating parts inside.
- Put the round-head bolt and a washer through the hole, then add the second washer and the locking nut.
- Hook the cable to both anchor points with the hooks snapped closed.
- On appliances with casters, permanently attach BK's warning label where it can be seen.
Finishing and leak testing
- Check that every connection is wrench-tight.
- Leak-test the final assembly per ANSI Z223.1/NFPA 54 or CSA B149.1. Never use an open flame or other ignition source to test. Rinse with water afterward so the test solution doesn't cause corrosion.
- Push the appliance into its normal position and make sure the hose isn't stressed by over-bending or kinking.
Common installation mistakes
BK's manual shows four: sharp bends, twists, double bends, and a hose that touches the floor.
Cleaning behind equipment (quick connect installations)
To disconnect: turn all gas supply and appliance knobs fully off. Pull back the coupler on the quick connect to release the hose nipple. Keep the hose and nipple clean and off the floor. Then unhook the restraining cable.
To reconnect: with the ball valve and appliance knobs still off, reattach the restraining cable. Pull back the coupler, push the nipple in until it clips into place, and tug lightly to confirm. There should be no gap between the sleeve and nipple. Turn the gas on at the ball valve and check for leaks.
Everyday care
- Clean connections with mild cleaning products and rinse with water immediately. Strong cleaners can permanently damage the connection points.
- Keep the hose away from anything over 230°F (110°C), and from objects, electrical wires or substances that could damage it.
- For stationary appliances, avoid unnecessary movement or vibration after installation. For appliances on casters, keep pulling and pushing to a minimum.
- Don't adjust or repair the quick connect; it has movable internal parts. If there's a problem, shut off the gas and call qualified personnel.
- Always follow the gas-flow arrows on the quick connect. It is not for dual-fed gas manifold lineups, where only the ball valve can be used.
- Never move an installed hose to another appliance. BK calls for a new hose and installation hardware for each installation.
Warranty
BK warrants its gas hoses against defects in material and workmanship for five years from purchase. Shut-off ball valves, quick connects, restraining cables and installation hardware are warranted for one year. The warranty doesn't cover shipping damage, accidents, alterations, unauthorized repair, failure to follow instructions, misuse or wear and tear, or hoses not installed to American Gas Association or American National Standards.
Gas capacity chart
BK's capacity figures (ANSI Z21.69 test method; natural gas, 0.64 specific gravity, 1,000 BTU per cubic foot, 0.5" water column pressure drop) are listed on each hose and kit page for that size. For capacity at 0.2" water column, multiply by 0.632. For other conditions, contact the manufacturer or your gas supplier.